有的(de)(de)管(guan)道設計(ji)(ji)人員因不(bu)清(qing)楚靜(jing)(jing)(jing)電(dian)(dian)接(jie)(jie)地(di)(di)范(fan)圍而引起設計(ji)(ji)事故,因此著(zhu)重講述。我(wo)國(guo)(guo)管(guan)道靜(jing)(jing)(jing)電(dian)(dian)接(jie)(jie)地(di)(di)和跨(kua)接(jie)(jie)相(xiang)關標準規范(fan)有GB12158《防止(zhi)靜(jing)(jing)(jing)電(dian)(dian)事故通(tong)用(yong)導則》、HG/T 20675《化工(gong)企業靜(jing)(jing)(jing)電(dian)(dian)接(jie)(jie)地(di)(di)設計(ji)(ji)規程(cheng)》、SH/T 3097《石(shi)油化工(gong)靜(jing)(jing)(jing)電(dian)(dian)接(jie)(jie)地(di)(di)設計(ji)(ji)規范(fan)》等(deng),GB 50235《工(gong)業金屬管(guan)道工(gong)程(cheng)施工(gong)規范(fan)》等(deng)規范(fan)也(ye)有專門的(de)(de)章節(jie)對(dui)管(guan)道靜(jing)(jing)(jing)電(dian)(dian)接(jie)(jie)地(di)(di)實施作出規定(ding)(ding)。ASME、PIP等(deng)國(guo)(guo)外(wai)標準規范(fan)也(ye)有具體(ti)規定(ding)(ding),國(guo)(guo)內外(wai)一些(xie)大型(xing)公(gong)司和工(gong)程(cheng)建(jian)設單位,對(dui)管(guan)道靜(jing)(jing)(jing)電(dian)(dian)接(jie)(jie)地(di)(di)設計(ji)(ji)有企業級(ji)的(de)(de)規定(ding)(ding)。
①. 位于爆(bao)(bao)炸和火(huo)災危(wei)險區(qu)內(nei)(nei)的管(guan)道應進行靜電接地(di)。在(zai)爆(bao)(bao)炸和火(huo)災危(wei)險區(qu)內(nei)(nei),可(ke)(ke)能存(cun)在(zai)可(ke)(ke)燃氣(qi)(qi)體和可(ke)(ke)燃粉塵積聚,如果(guo)產生(sheng)電火(huo)花(hua),可(ke)(ke)能引起火(huo)災或(huo)(huo)爆(bao)(bao)炸事故。為了(le)防(fang)止(zhi)在(zai)電氣(qi)(qi)設(she)施使用過程中產生(sheng)電火(huo)花(hua),引燃或(huo)(huo)引爆(bao)(bao)可(ke)(ke)燃氣(qi)(qi)體或(huo)(huo)可(ke)(ke)燃粉塵,爆(bao)(bao)炸和火(huo)災危(wei)險區(qu)內(nei)(nei)的強、弱(ruo)電設(she)施均需要(yao)選用防(fang)爆(bao)(bao)型。
②. 氧氣(qi)(qi)管道(dao)(dao)應進(jin)行(xing)靜電接地。氧氣(qi)(qi)是(shi)一種特殊的介(jie)質(zhi),其本身不燃燒,卻是(shi)強(qiang)氧化劑,在(zai)純氧的環(huan)境(jing)中,鋼管會被點燃。因此雖然氧氣(qi)(qi)不屬于可燃介(jie)質(zhi),但純氧管道(dao)(dao)必須良好接地。
③. 氣(qi)(qi)固管(guan)道應進行靜電(dian)接地(di)。氣(qi)(qi)固管(guan)道在(zai)運行過程中會產生大量靜電(dian),必須(xu)保(bao)證管(guan)道良好接地(di),防(fang)止大量靜電(dian)集聚(ju)。
④. 平行(xing)(xing)敷設(she)的管(guan)道(dao),凈距小于100mm時,應每隔20m,設(she)置靜電(dian)跨(kua)(kua)接。近距離平行(xing)(xing)敷設(she)的管(guan)廊(lang),為保證兩根(gen)管(guan)道(dao)等電(dian)位,需要每隔20m設(she)置跨(kua)(kua)接。
⑤. 管(guan)(guan)道(dao)進出裝置界區處(chu)應進行(xing)靜電接地,防止界外管(guan)(guan)道(dao)和裝置內管(guan)(guan)道(dao)間電荷的相互轉移。